Industrial hall interior seen toward the roof: open smoke vents letting in beams of natural light (illustrative generated image)

Technical tool

Indicative natural smoke-ventilation calculator

The tool sizes natural smoke ventilation: the required aerodynamic area (P118/1:2025, Table 121), the number of smoke vents, the 1 vent / 200 m² check and make-up air (75%, Cv per Table 119). Results are indicative, not professional design.

CALC-DSF / P118:2025

Simplified P118/1:2025 method — natural smoke ventilation

Indicative result

The tool sizes natural smoke ventilation only — smoke vents and rooflights with smoke vents, the solutions DASITRADE offers.

Step 1

The building

The data the simplified method actually uses: space type, floor area and thermal load density q.

Space and thermal load

Determined per SR 10903-2. Thresholds (Art. 2.1.2.2): low ≤ 420 · medium ≤ 840 · high ≤ 1680 · very high > 1680.

For the sketch and dimension lines only — it does not enter the P118 calculation.

Vent and make-up air
Vent base height

Step 2

The sizing

Required aerodynamic area (Table 121), number of vents, the 1 vent / 200 m² check and make-up air (75 %).

Within the simplified method · medium risk

Schematic section — hall with roof smoke ventsThe smoke layer collects under the roof and leaves through the roof vents; make-up air enters through openings in the lower part. The h dimension and area A reflect the entered values; the number of drawn vents follows the calculation result.smoke layer (schematic)5 × vent 2000×2000 mm · base 350 mmair intake — lower part · Av ≥ 15 m²h = 8 mA = 1,000 m²INDICATIVE SCHEMATIC · NOT TO SCALE
Final placement is established by the design. Natural venting exhausts hot smoke through roof vents using thermal buoyancy; fresh air enters low down. The required aerodynamic area grows with thermal load density q (Table 121): 1% at low risk up to over 3% at very high risk. At least one vent per 200 m² is provided.

Required Aa

11.071 m²

Applied ratio: 1.11 % — Tabelul 121 (Art. 8.7.3) — interpolare pe q

Smoke vents

5 × 2000×2000 mm

  • from required Aa: 4
  • from the 1 vent / 200 m² rule: 5
  • final count = the larger of the two

Provided Aa

14 m²

coverage 126.5 %

Make-up air — Aa (≥ 75 %)

10.5 m²

geometric area Av ≥ 15 m², with Cv 0.7 (Free opening)

Constraints and restrictions

  • Smoke reservoir ≤ 2,000 m² (natural, Art. 8.1.13). Input area: 1000 m².
  • Reservoir length ≤ 60 m on any axis (Art. 8.1.12(3)); smoke screens ≥ 50 cm, min class DH 30 (Art. 8.1.3(2)) — verify on actual geometry.
Calculation steps (traceability)
StepFormulaValuesResultSource
Applied ratioraport(q, spațiu)q = 600 MJ/m²1.11 %Tabelul 121 (Art. 8.7.3) — interpolare pe q
Required AaAa = raport × A1.11% × 1,000 m²11.071 m²P118 Art. 8.7.3 (Tabelul 121)
Count from Aa⌈Aa / Aa_trapă⌉Aa_trapă = 2.8 m²4EN 12101-2 (Aa = Av × Cv)
Count from 200 m² rule⌈A / 200⌉A = 1,000 m²5P118 Art. 8.2.4(4)
Final countmax(cele două)max(4, 5)5—
Provided AaN × Aa_trapă5 × 2.814 m² (126.5%)—
Make-up airAa_adm ≥ 75% × Aa14 m²10.5 m²P118 Art. 8.2.1(2)
Geometric intake areaAv = Aa_adm / CvCv = 0.715 m²P118 Art. 8.2.6 (Tabelul 119)

Step 3

The right product

The GULAJSKI smoke vent that covers the need, the equipment and the quote request.

Smoke vent 2000×2000 mm

EN 12101-2 · certificate 1396-CPR-0197 · DoP Klapa 1/09/2024

Configuration
5 × 2000×2000 mm
Aa per vent (base 350 mm)
2.8 m²
Geometric area Av per vent
4 m²

Declared envelope of the GULAJSKI range (DoP): Aa 0.429–4.500 m² per vent.

Equipment and actuation

  • Pneumatic CO₂ actuation: 1 cartridge/hatch × 55 g → total 275 g. Automatic release via thermal valve (thermobulb).
  • Electric 24V actuation is not feasible at this size (per GULAJSKI table) — CO₂ only.

Products for natural smoke ventilation

Indicative summary (for the quote request)

Natural smoke and heat venting — indicative sizing per the simplified P118/1:2025 method (Table 121). For A = 1000 m², q = 600 MJ/m² (mijlociu risk), ratio 1.11% → required Aa = 11.071 m². Provide 5 GULAJSKI 2000×2000 mm smoke vents (base H350, EN 12101-2, cert 1396-CPR-0197), unit Aa 2.8 m² → provided Aa 14 m² (coverage 126.5%; min 1 vent/200 m² → 5). Make-up air at low level: Aa ≥ 10.5 m² (75% of exhaust, Art. 8.2.1), geometric area Av ≥ 15 m² (Cv 0.70, Free opening). Pneumatic CO₂ actuation: 1 cartridge/hatch × 55 g → total 275 g. Automatic release via thermal valve (thermobulb). Indicative document — does not replace professional fire-safety design.

Request a quote

Indicative tool, based on the simplified P118/1:2025 method (Ch. 8.7) and GULAJSKI product data (cert 1396-CPR-0197). It does NOT replace design, the fire-safety scenario, or specialist verification. q is determined per SR 10903-2.

Choose which cookies you accept. You can change them at any time from the “Cookie settings” button in the corner of the page or from the website footer.

  • Strictly necessaryEssential for the website to work. Cookie: cookie_consent (DASITRADE) — stores your cookie choices, up to 180 days. Cannot be switched off. Cloudflare technical cookies (Cloudflare, Inc.): __cf_bm — tells visitors apart from automated bots, 30 minutes; cf_clearance — only after a security check.Always on