Technical tool
Indicative natural smoke-ventilation calculator
The tool sizes natural smoke ventilation: the required aerodynamic area (P118/1:2025, Table 121), the number of smoke vents, the 1 vent / 200 m² check and make-up air (75%, Cv per Table 119). Results are indicative, not professional design.
CALC-DSF / P118:2025
Simplified P118/1:2025 method — natural smoke ventilation
Indicative result
The tool sizes natural smoke ventilation only — smoke vents and rooflights with smoke vents, the solutions DASITRADE offers.
Step 1
The building
The data the simplified method actually uses: space type, floor area and thermal load density q.
Step 2
The sizing
Required aerodynamic area (Table 121), number of vents, the 1 vent / 200 m² check and make-up air (75 %).
Within the simplified method · medium risk
Required Aa
11.071 m²
Applied ratio: 1.11 % — Tabelul 121 (Art. 8.7.3) — interpolare pe q
Smoke vents
5 × 2000×2000 mm
- from required Aa: 4
- from the 1 vent / 200 m² rule: 5
- final count = the larger of the two
Provided Aa
14 m²
coverage 126.5 %
Make-up air — Aa (≥ 75 %)
10.5 m²
geometric area Av ≥ 15 m², with Cv 0.7 (Free opening)
Constraints and restrictions
- Smoke reservoir ≤ 2,000 m² (natural, Art. 8.1.13). Input area: 1000 m².
- Reservoir length ≤ 60 m on any axis (Art. 8.1.12(3)); smoke screens ≥ 50 cm, min class DH 30 (Art. 8.1.3(2)) — verify on actual geometry.
Calculation steps (traceability)
| Step | Formula | Values | Result | Source |
|---|---|---|---|---|
| Applied ratio | raport(q, spațiu) | q = 600 MJ/m² | 1.11 % | Tabelul 121 (Art. 8.7.3) — interpolare pe q |
| Required Aa | Aa = raport × A | 1.11% × 1,000 m² | 11.071 m² | P118 Art. 8.7.3 (Tabelul 121) |
| Count from Aa | ⌈Aa / Aa_trapă⌉ | Aa_trapă = 2.8 m² | 4 | EN 12101-2 (Aa = Av × Cv) |
| Count from 200 m² rule | ⌈A / 200⌉ | A = 1,000 m² | 5 | P118 Art. 8.2.4(4) |
| Final count | max(cele două) | max(4, 5) | 5 | — |
| Provided Aa | N × Aa_trapă | 5 × 2.8 | 14 m² (126.5%) | — |
| Make-up air | Aa_adm ≥ 75% × Aa | 14 m² | 10.5 m² | P118 Art. 8.2.1(2) |
| Geometric intake area | Av = Aa_adm / Cv | Cv = 0.7 | 15 m² | P118 Art. 8.2.6 (Tabelul 119) |
Step 3
The right product
The GULAJSKI smoke vent that covers the need, the equipment and the quote request.
Smoke vent 2000×2000 mm
EN 12101-2 · certificate 1396-CPR-0197 · DoP Klapa 1/09/2024
- Configuration
- 5 × 2000×2000 mm
- Aa per vent (base 350 mm)
- 2.8 m²
- Geometric area Av per vent
- 4 m²
Declared envelope of the GULAJSKI range (DoP): Aa 0.429–4.500 m² per vent.
Equipment and actuation
- Pneumatic CO₂ actuation: 1 cartridge/hatch × 55 g → total 275 g. Automatic release via thermal valve (thermobulb).
- Electric 24V actuation is not feasible at this size (per GULAJSKI table) — CO₂ only.
Products for natural smoke ventilation
Indicative summary (for the quote request)
Natural smoke and heat venting — indicative sizing per the simplified P118/1:2025 method (Table 121). For A = 1000 m², q = 600 MJ/m² (mijlociu risk), ratio 1.11% → required Aa = 11.071 m². Provide 5 GULAJSKI 2000×2000 mm smoke vents (base H350, EN 12101-2, cert 1396-CPR-0197), unit Aa 2.8 m² → provided Aa 14 m² (coverage 126.5%; min 1 vent/200 m² → 5). Make-up air at low level: Aa ≥ 10.5 m² (75% of exhaust, Art. 8.2.1), geometric area Av ≥ 15 m² (Cv 0.70, Free opening). Pneumatic CO₂ actuation: 1 cartridge/hatch × 55 g → total 275 g. Automatic release via thermal valve (thermobulb). Indicative document — does not replace professional fire-safety design.
Indicative tool, based on the simplified P118/1:2025 method (Ch. 8.7) and GULAJSKI product data (cert 1396-CPR-0197). It does NOT replace design, the fire-safety scenario, or specialist verification. q is determined per SR 10903-2.