Continuous rooflights
Continuous rooflight with smoke vent
pneumatic, polycarbonate
Arched continuous rooflight with an integrated single-leaf smoke vent and pneumatic CO₂ actuation, for natural daylighting and smoke & heat exhaust. Multiwall polycarbonate glazing. Classified to EN 12101-2:2003.
- Harmonised standard:
- EN 12101-2:2003
- Aa:
- 0.429 – 4.275 m²
- Product code:
- GUL-KD-PSM
Photo: GULAJSKI
Documents & certification
- Harmonised standard
- EN 12101-2:2003
- Assessment system (AVCP)
- 1
- Notified body
- FIRES s.r.o., Batizovce (NB 1396)
- CPR certificate
- 1396-CPR-0226
- Declaration of performance
- Klapa 3/01/2022
- Manufacturer
- GULAJSKI · KD PSM
- Product code
- GUL-KD-PSM
- DTR 13 (07.2026) — Technical and operational documentation / installation instructions
- Klapa 3/01/2022 — Declaration of performance (EN 12101-2:2003)
- 1396-CPR-0226 — Certificate of constancy of performance (FIRES s.r.o., NB 1396)
The documents are provided on request, at office@dasitrade.ro.
Request the documentsHow many vents do you need? Indicative smoke-ventilation calculator (P118/1:2025)
Description
GULAJSKI continuous rooflights (light bands) are systemic roof assemblies that, in normal operation, provide natural daylighting through the roof slope. The single-leaf smoke vents integrated in the rooflight naturally exhaust smoke and hot gases from the areas over which they are installed.
The band is arched and is installed on flat or low-slope roofs, on bases raised above the roof surface (continuous or point support, self-supporting). The structure is made of aluminium profiles filled with multiwall polycarbonate sheets; it is delivered in segments, for made-to-order lengths.
In a fire, the vent opens to at least 140° via the pneumatic CO₂ system, keeping the lower part of the room free of smoke. In normal operation the rooflight can also serve a ventilation function.
Applications
- Natural daylighting of halls, with integrated smoke exhaust
- Flat or low-slope roofs (industrial, commercial, logistics)
- Element of a gravitational smoke and heat exhaust system (SHEVS)
- Areas needing a continuous light band plus smoke ventilation on one structure
Technical specifications
| Shape | Arched continuous band (also triangular / “along-ridge” variants) |
|---|---|
| Span (band width) | 1000–6000 mm |
| Vent opening angle | min. 140° |
| Actuation | Pneumatic CO₂ (20–150 g cartridge automatic / up to 1500 g manual) |
| Thermal trigger | Thermo bulb 68 °C (standard); optional 93 / 110 / 141 / 182 °C |
| Activation | Automatic (thermo bulb) or manual (alarm-box button); optional 24 V DC solenoid valve linked to the fire panel |
| Glazing | Multiwall polycarbonate PC-10 / PC-16 / PC-20; optional fire-retardant NRO – Broof(t1); clear or opal |
| Structure | Drawn aluminium profiles (optionally powder-coated / anodised) |
| Base | Galvanised steel or aluminium sheet; continuous or point support (self-supporting); optional C1–C5 paint |
| Additional function | Ventilation in normal operation |
| Installation | By the manufacturer’s teams or authorised/trained units |
Declared performance
| Code | Characteristic | Declared value |
|---|---|---|
| Aa | Aerodynamic free areaPer product label, depending on size | 0.429 – 4.275 m² |
| Re | Reliability | Re 1000 |
| SL | Opening under load (snow) | SL 250 – SL 950 |
| WL | Wind load | WL 1500 |
| B | High-temperature resistance | B 300 |
| — | Resistance to wind-induced vibration | > 10 Hz |
| — | Logarithmic decrement | > 0.1 |
| — | Ventilation (cycles) | 10 000 |
| — | External fire performanceNPD — no performance determined | NPD |
Dimensions
Modular arched band: span (width) 1000–6000 mm; made-to-order length, from segments. Glazing thicknesses: PC-10 / PC-16 / PC-20.