Smoke vents
Z smoke vent
single-leaf, electric actuator, polycarbonate
Single-leaf roof smoke vent with multiwall polycarbonate glazing and 24 V DC electric actuation, for natural smoke and heat exhaust. Classified to EN 12101-2:2003.
- Harmonised standard:
- EN 12101-2:2003
- Aa:
- 0.429 – 4.500 m²
- Product code:
- GUL-KD-Z-EL
Photo: GULAJSKI
Documents & certification
- Harmonised standard
- EN 12101-2:2003
- Assessment system (AVCP)
- 1
- Notified body
- FIRES s.r.o., Batizovce (NB 1396)
- CPR certificate
- 1396-CPR-0197
- Declaration of performance
- Klapa 1/09/2024
- Manufacturer
- GULAJSKI · Gulajski Z
- Product code
- GUL-KD-Z-EL
- DTR 03 (04.2025) — Technical and operational documentation / installation instructions
- Klapa 1/09/2024 — Declaration of performance (EN 12101-2:2003)
- 1396-CPR-0197 — Certificate of constancy of performance (FIRES s.r.o., NB 1396)
The documents are provided on request, at office@dasitrade.ro.
Request the documentsHow many vents do you need? Indicative smoke-ventilation calculator (P118/1:2025)
Description
The Gulajski "Z" smoke vent is a natural smoke and heat exhaust device installed on the roofs of single-storey buildings and on flat roofs above the top storey of multi-storey buildings. In a fire it opens to at least 140°, keeping the lower part of the room free of smoke to aid evacuation and rescue.
The tilting segment consists of an aluminium- and PVC-chamber-profile frame, sealed around its full perimeter, and a multiwall polycarbonate cover (opal or transparent; other colours on request). The galvanised steel base is made in a straight or straight-slant variant.
In normal operation the vent works as a rooflight in the roof slope and can also serve a ventilation function.
Applications
- Roofs of single-storey buildings (e.g. industrial, commercial, logistics halls)
- Flat roofs above the top storey of multi-storey buildings
- Element of a gravitational smoke and heat exhaust system (SHEVS)
- Dual rooflight and ventilation function in normal operation
Technical specifications
| Opening angle | min. 140° |
|---|---|
| Glazing | Multiwall polycarbonate (opal or transparent; other colours on request) |
| Tilting-segment frame | Aluminium profiles + PVC chamber profile, perimeter seals |
| Base | Galvanised steel sheet, straight or straight-slant, min. 1.25 mm thick, height 350–699 mm |
| Base insulation | Mineral wool / polystyrene, min. 40 mm |
| Hinges | 2–5 stainless steel hinges (depending on size) |
| Actuator | 1 × electric, type SG13÷120, stroke 435–1060 mm, 24 V DC |
| Control unit | Maintenance-free, 230 V AC (24 V DC power supply) |
| Emergency power | Batteries — 72 h backup |
| Activation | Automatic (smoke/heat detectors) or manual (alarm button); signal from the fire alarm system |
| Periodic inspections | At least once a year (per regulations); manufacturer recommends twice a year |
Declared performance
| Code | Characteristic | Declared value |
|---|---|---|
| Aa | Aerodynamic free areaPer product label, depending on size | 0.429 – 4.500 m² |
| Re | Reliability | Re 1000 |
| SL | Opening under load (snow) | SL 250 – SL 950 |
| WL | Wind load | WL 1000 – WL 1500 |
| B | High-temperature resistance | B 300 |
| — | Resistance to wind-induced vibration | > 10 Hz |
| — | Logarithmic decrement | > 0.1 |
| — | Ventilation (cycles) | 10 000 |
| — | External fire performanceNPD — no performance determined | NPD |
Dimensions
Standard sizes (cm); other sizes on request.
- 100×100
- 100×130
- 100×150
- 100×180
- 100×200
- 120×120
- 130×130