Skip to content

Smoke vents

Z smoke vent

single-leaf, electric actuator, polycarbonate

Single-leaf roof smoke vent with multiwall polycarbonate glazing and 24 V DC electric actuation, for natural smoke and heat exhaust. Classified to EN 12101-2:2003.

Request a quote
Harmonised standard:
EN 12101-2:2003
Aa:
0.429 – 4.500 m²
Product code:
GUL-KD-Z-EL

Photo: GULAJSKI

Documents & certification

Harmonised standard
EN 12101-2:2003
Assessment system (AVCP)
1
Notified body
FIRES s.r.o., Batizovce (NB 1396)
CPR certificate
1396-CPR-0197
Declaration of performance
Klapa 1/09/2024
Manufacturer
GULAJSKI · Gulajski Z
Product code
GUL-KD-Z-EL
  • DTR 03 (04.2025) — Technical and operational documentation / installation instructions
  • Klapa 1/09/2024 — Declaration of performance (EN 12101-2:2003)
  • 1396-CPR-0197 — Certificate of constancy of performance (FIRES s.r.o., NB 1396)

The documents are provided on request, at office@dasitrade.ro.

Request the documents
Request a quote

How many vents do you need? Indicative smoke-ventilation calculator (P118/1:2025)

Description

The Gulajski "Z" smoke vent is a natural smoke and heat exhaust device installed on the roofs of single-storey buildings and on flat roofs above the top storey of multi-storey buildings. In a fire it opens to at least 140°, keeping the lower part of the room free of smoke to aid evacuation and rescue.

The tilting segment consists of an aluminium- and PVC-chamber-profile frame, sealed around its full perimeter, and a multiwall polycarbonate cover (opal or transparent; other colours on request). The galvanised steel base is made in a straight or straight-slant variant.

In normal operation the vent works as a rooflight in the roof slope and can also serve a ventilation function.

Applications

  • Roofs of single-storey buildings (e.g. industrial, commercial, logistics halls)
  • Flat roofs above the top storey of multi-storey buildings
  • Element of a gravitational smoke and heat exhaust system (SHEVS)
  • Dual rooflight and ventilation function in normal operation

Technical specifications

Technical specifications
Opening anglemin. 140°
GlazingMultiwall polycarbonate (opal or transparent; other colours on request)
Tilting-segment frameAluminium profiles + PVC chamber profile, perimeter seals
BaseGalvanised steel sheet, straight or straight-slant, min. 1.25 mm thick, height 350–699 mm
Base insulationMineral wool / polystyrene, min. 40 mm
Hinges2–5 stainless steel hinges (depending on size)
Actuator1 × electric, type SG13÷120, stroke 435–1060 mm, 24 V DC
Control unitMaintenance-free, 230 V AC (24 V DC power supply)
Emergency powerBatteries — 72 h backup
ActivationAutomatic (smoke/heat detectors) or manual (alarm button); signal from the fire alarm system
Periodic inspectionsAt least once a year (per regulations); manufacturer recommends twice a year

Declared performance

Declared performance
CodeCharacteristicDeclared value
AaAerodynamic free areaPer product label, depending on size0.429 – 4.500 m²
ReReliabilityRe 1000
SLOpening under load (snow)SL 250 – SL 950
WLWind loadWL 1000 – WL 1500
BHigh-temperature resistanceB 300
—Resistance to wind-induced vibration> 10 Hz
—Logarithmic decrement> 0.1
—Ventilation (cycles)10 000
—External fire performanceNPD — no performance determinedNPD

Dimensions

Standard sizes (cm); other sizes on request.

  • 100×100
  • 100×130
  • 100×150
  • 100×180
  • 100×200
  • 120×120
  • 130×130

Choose which cookies you accept. You can change them at any time from the “Cookie settings” button in the corner of the page or from the website footer.

  • Strictly necessaryEssential for the website to work. Cookie: cookie_consent (DASITRADE) — stores your cookie choices, up to 180 days. Cannot be switched off. Cloudflare technical cookies (Cloudflare, Inc.): __cf_bm — tells visitors apart from automated bots, 30 minutes; cf_clearance — only after a security check.Always on

Full details in the Cookie policy.