Tools and standards

Technical centre

The indicative natural smoke-ventilation calculator built on the simplified P118/1:2025 method, the choice of vent by building type, and the index of applicable legislation, each entry pointing to the official version.

P118/1:2025 calculator

Indicative smoke-ventilation calculator (P118/1:2025)

Aerodynamic area and vent count for natural smoke ventilation (Table 121) and make-up air intake (75%, Cv per Table 119). Indicative — it does not replace design.

Open calculator

Choosing the product

Which vent the building calls for

In natural smoke ventilation, hot smoke rises and leaves through automatically-opening vents placed at the top of the space, while make-up air enters through openings in the lower third — with an aerodynamic area of at least 75% of the exhaust area (P118/1:2025 art. 8.1.10, 8.2.1). The exhaust devices must be certified to EN 12101-2, sizing uses the aerodynamic free area Aa (not the geometric area), and where smoke vents are used at least one vent is provided per 200 m² of floor (art. 8.2.4).

Industrial and production halls

Natural roof venting with Gulajski Z point smoke vents (cert. 1396-CPR-0197), spread uniformly — at least one vent per 200 m² of floor (art. 8.2.4) — with the combined aerodynamic area set by the fire-load density q (Table 121: from 1% of the floor area, rising with q). Smoke screens of at least DH 30, dropped at least 50 cm below the roof, divide the space into reservoirs of at most 2,000 m² (art. 8.1.12–8.1.13), and make-up air is provided through openings in the lower third of the walls.

ProductsZ smoke vent — single-leaf, electric actuator, polycarbonate · Continuous rooflight with smoke vent — pneumatic, polycarbonate

Warehouses and logistics spaces

With combustible goods and packaging, the fire-load density q is usually high, so the required exhaust ratio rises per Table 121 (up to 1:30 for q > 4,200 MJ/m²) — 1% is only the minimum. The Gulajski Z vent (Aa 0.429–4.500 m²) and the vent integrated in the KD PSM rooflight band (Aa 0.429–4.275 m², cert. 1396-CPR-0226) apply, both EN 12101-2, class B 300 and Re 1000, dual-function — tested to 10,000 daily-ventilation cycles; the SL (snow) and WL (wind) classes are checked against the site.

ProductsZ smoke vent — single-leaf, electric actuator, polycarbonate · Continuous rooflight with smoke vent — pneumatic, polycarbonate

Commercial spaces

For single-level sales floors, natural venting runs through roof vents — KD PSM in a rooflight band where daylight is also needed, or Gulajski Z point vents — with smoke reservoirs of at most 2,000 m² and at least one vent per 200 m². For atria, the automatically-opening devices provide a free area of at least 1% of the largest atrium level when q < 105 MJ/m² (but no less than 2 m²), or at least 5% above that threshold or with adjacent retail functions (art. 8.6.1).

ProductsContinuous rooflight with smoke vent — pneumatic, polycarbonate · Z smoke vent — single-leaf, electric actuator, polycarbonate

Stairwells

Where the code provides for natural smoke exhaust from the stairwell (art. 2.5.6.1.2), an automatically-opening vent placed in the upper third of the top level discharges smoke directly outdoors; its aerodynamic free area is at least 1 m² (art. 8.1.9), with make-up air entering at the bottom of the stair (at least 75% of the free exhaust area, art. 8.1.10). A Gulajski Z vent certified to EN 12101-2 can fill this role.

ProductsZ smoke vent — single-leaf, electric actuator, polycarbonate

Daylight and roof access

The polycarbonate point rooflight (EN 1873) and the roof access hatch provide daylighting and access respectively — on any building type. They are not smoke-ventilation devices: without EN 12101-2 classes, they cannot be counted as smoke-exhaust area. Where the same opening must deliver both daylight and smoke exhaust, the solution is the KD PSM rooflight band with an integrated smoke vent, certified to EN 12101-2.

ProductsPoint rooflight — polycarbonate, fixed or vented · Roof access hatch — polycarbonate, with gas springs · Continuous rooflight with smoke vent — pneumatic, polycarbonate

The information is indicative and does not replace specialist design or verification.

Standards

Smoke-ventilation legislation, searchable

Search by code or article, each entry pointing to the official version of the act.

12 results

  • P118/1-2025MDLPA (România)

    Code on fire safety of buildings, Part I — Buildings

    It is the primary instrument for smoke ventilation in Romania. Chapter 8 covers smoke and hot-gas exhaust, including the simplified sizing method for natural smoke ventilation (Table 121) and special cases (atrium, stairwells).

    Key points
    • Simplified natural method: free aerodynamic area related to floor area by a ratio that increases with thermal load density q (Table 121, art. 8.7.3).
    • Make-up (inlet) air must provide at least 75% of the exhaust (art. 8.2.1(2), art. 8.3.1(4)).
    • At least one exhaust point per maximum 200 m² of floor (art. 8.2.4(4)).
  • P118/2-2013MDLPA (România)

    Fire-safety code, Part II — Fire-extinguishing installations

    Coordinates with smoke ventilation: automatic suppression affects the fire-safety scenario and the smoke-ventilation sizing method.

    Key points
    • The sprinkler–smoke-ventilation interaction is part of the fire-safety scenario.
    • The fire-safety scenario integrates extinguishing and smoke exhaust.
  • P118/3-2015MDLPA (România)

    Fire-safety code, Part III — Detection, signalling and alarm installations

    Detection triggers the smoke-control systems (automatic opening of the smoke vents). The control interface is part of the smoke-control solution.

    Key points
    • Automatic activation of smoke ventilation on fire detection.
    • The detection–smoke-ventilation interface is part of the safety scenario.
  • SR EN 12101-1ASRO / CEN

    Smoke and heat control systems. Part 1: Smoke barriers

    Smoke barriers form the smoke reservoir needed for effective smoke ventilation in halls, atria and large spaces.

    Key points
    • Delimiting the smoke reservoir under the roof.
    • Screen performance class (e.g. DH) by temperature and time.
  • SR EN 12101-2ASRO / CEN

    Smoke and heat control systems. Part 2: Natural smoke and heat exhaust ventilators

    The harmonised standard under which the GULAJSKI smoke vents (Gulajski Z and KD PSM) are certified. Free aerodynamic area Aa and classes (Re, SL, WL, T, B) come from this standard and the DoP.

    Key points
    • Aa (free aerodynamic area) = Av × Cv, always smaller than the geometric area; Aa is used for sizing.
    • Declared classes: Re (reliability/cycles), SL (snow load), WL (wind load), B (heat exposure, e.g. B300 = 300 °C/30 min).
    • Assessed under AVCP system 1, with a notified body (e.g. FIRES NB 1396).
  • SR EN 12101-5ASRO / CEN (raport tehnic)

    Smoke and heat control systems. Part 5: Functional recommendations and calculation methods

    The basis of the "complex method" for non-standard cases (mall, large atrium, complex-geometry industrial) where the P118 simplified method is not sufficient — requires an authorised designer.

    Key points
    • Smoke-layer, reservoir and clear-layer-height model.
    • Applied where the P118 simplified method does not cover the case.
  • SR EN 1873ASRO / CEN

    Plastic rooflights (unit skylights) — product specification

    The standard for the GULAJSKI point rooflight. Note: a rooflight classified only to EN 1873 (without EN 12101-2 classes) is NOT a smoke-ventilation device — it serves daylighting/ventilation, not smoke exhaust.

    Key points
    • Daylighting + everyday ventilation, not smoke exhaust.
    • The EN 1873 vs EN 12101-2 distinction is essential when reading datasheets.
  • Legea 307/2006Parlamentul României

    Law on fire defence

    Sets the obligations of owners and designers and the framework requiring fire-safety measures, including smoke control.

    Key points
    • General fire-defence obligations.
    • Framework for ISU (fire authority) endorsement/authorisation.

Regulatory framework

The framework codes

P118/1:2025 — the framework code for smoke ventilation

P118/1:2025 is the Romanian regulation that guides smoke-ventilation sizing. For ordinary rooms and smoke reservoirs it allows a simplified method (art. 8.7), applicable to natural extraction (Table 121); non-standard cases — malls, large atria, industrial buildings or complex geometries (art. 8.1.2(1)) — require the complex method based on SR CEN/TR 12101-5 and a licensed designer.

The starting point of any sizing is the fire risk, classified by the fire load density q (art. 2.1.2.2(1)): low (q ≤ 420 MJ/m²), medium, high and very high.

SourcesP118/1:2025 art. 8.1.2(1)P118/1:2025 art. 2.1.2.2(1)

The link to the project: from classes to site data

A product's declared classes are not chosen at random — they are matched to the project data. For natural vents (EN 12101-2), the snow-load class SL is chosen at least equal to the site's snow load (established per EN 1991-1-3), while the wind-load class WL follows the wind action computed per EN 1991-1-4.

A project therefore has three levels: the code sets the requirement, the EN classes describe what the product delivers, and the site data fix the minimum class. The final matching remains indicative and rests with the authorised specialist.

SourcesEN 12101-2EN 1991-1-3EN 1991-1-4

Indicative information, for guidance. It does not replace design, verification, or the official, complete and current version of the codes and standards applicable to the project.

Choose which cookies you accept. You can change them at any time from the “Cookie settings” button in the corner of the page or from the website footer.

  • Strictly necessaryEssential for the website to work. Cookie: cookie_consent (DASITRADE) — stores your cookie choices, up to 180 days. Cannot be switched off. Cloudflare technical cookies (Cloudflare, Inc.): __cf_bm — tells visitors apart from automated bots, 30 minutes; cf_clearance — only after a security check.Always on